DK Digital CDB-700 Instruction Manual Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 82
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
4. SETTING
IMR02C16-E3
14
Continued from the previous page.
7. Enable communication
parameter
After all the communications parameters are
set, perform one of the following steps to make
settings valid:
The power is turned on again after turning
it off once.
The RUN/STOP mode is changed to RUN
from STOP again after changing it to
STOP once.
If you changed the communication
parameters, be sure to turn the power
OFF and then ON or switch from
STOP to RUN.
If this is not done, the higher level
device will not be able to recognize the
changed values and communication
may not be possible.
Set the data bit configuration. As an example,
factory set value “0 (data
b
it 8, without parit
y
bit, stop bit 1)” is set.
Data bit configuration
For details of setting range, refer to
Data bit configuration table (P. 10).
Press the SET key.
The display goes to the interval time.
Data bit configuration
Interval time
Interval time
Set the interval time.
As an example, factory set value “10” is set.
Setting range: 0 to 250 ms
Press the SET key.
The display goes to the communication
response monitor.
Communication
response monitor
Interval time