DK Digital CDB-700 Instruction Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 82
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
2. SPECIFICATIONS
IMR02C16-E3
4
Modbus
Interface: Based on RS-485, EIA standard
Connection method: 2-wire system, half-duplex multi-drop connection
Synchronous method: Start-stop synchronous type
Communication speed: 2400 bps, 4800 bps, 9600 bps, 19200 bps
Data bit configuration: Start bit: 1
Data bit: 8
Parity bit: Without, Odd or Even
Stop bit: 1 or 2
Protocol: Modbus
Signal transmission mode: Remote Terminal Unit (RTU) mode
Function code: 03H (Read holding registers)
06H (Preset single register)
08H (Diagnostics: loopback test)
Error check method: CRC-16
Error code: 1: Function code error
2: When the mismatched address is specified
3: When the specified number of data items in the query message exceeds
the maximum number of data items available
4: Self-diagnostic error response
Termination resistor: Externally terminal connected (Example: 120 1/2 W)
Maximum connections: Up to 31 controllers
Loader communication
Connection method: Connection with a loader communication cable for RKC USB converter
COM-K (sold separately).
Synchronous method: Start-stop synchronous type
Communication speed: 9600 bps
Data bit configuration: Start bit: 1
Data bit: 8
Parity bit: Without
Stop bit: 1
The data bit configuration is fixed.
The device address is fixed to “0.”
Protocol: RKC communication protocol
(ANSI X3.28-1976 subcategories 2.5 and A4)
Maximum connections: 1 controller